Requirement Details
Electron Ion Collider

F-ESR-RF.01.06
Requirement details, history, relationships and interfaces associated with requirement F-ESR-RF.01.06
CURRENT RECORD
ARCHIVE RECORDS
RELATIONSHIPS
INTERFACES
| Record Date: 02/09/2026 20:55 | |||
| Identifier: | F-ESR-RF.01.06 | WBS: | 6.02.02 |
| Date Modified: | TBD: | FALSE | |
| Status Date: | Status: | Approved | |
| Description: | The ESR RF Systems shall interface to all required accelerator systems. | ||
| Comments: | |||
| Record Date: 05/16/2025 17:04 | |||
| Identifier: | F-ESR-RF.01.06 | WBS: | 6.08 |
| Date Modified: | TBD: | FALSE | |
| Status Date: | Status: | Approved | |
| Description: | The ESR RF Systems shall interface to all required accelerator systems. | ||
| Comments: | |||
| Record Date: 05/15/2025 20:34 | |||
| Identifier: | F-ESR-RF.01.06 | WBS: | |
| Date Modified: | TBD: | FALSE | |
| Status Date: | Status: | ||
| Description: | The ESR RF Systems shall interface to all required accelerator systems. | ||
| Comments: | |||
| Record Date: 03/13/2025 17:22 | |||
| Identifier: | F-ESR-RF.01.06 | WBS: | 6.08 |
| Date Modified: | TBD: | FALSE | |
| Status Date: | Status: | Approved | |
| Description: | The ESR RF Systems shall interface to all required accelerator systems. | ||
| Comments: | |||
| Parents | |
| No parents. | |
| Children | |
| P-ESR-RF-ACAV:591S-FA.02.04 | The SRF Cryomodule cavity helium jacket shall have a minimum helium bath vapor surface area of 0.049 m^2. |
| P-ESR-RF-ACAV:591S-FA.02.05 | The maximum designed helium supply operational temperature shall be 5.5 K. |
| P-ESR-RF-ACAV:591S-FA.02.06 | The range of the designed helium supply operational pressure shall be 3 to 3.5 bar. |
| P-ESR-RF-ACAV:591S-FA.02.07 | The range of the designed combined helium return temperature shall be 20 to 100 K. |
| P-ESR-RF-ACAV:591S-FA.02.08 | The range of the designed combined helium return pressure shall be 2.4 to 2.6 bar. |
| P-ESR-RF-ACAV:591S-FA.02.09 | The maximum designed sub-atmospheric helium return temperature shall be 4.5 K. |
| P-ESR-RF-ACAV:591S-FA.02.10 | The maximum designed sub-atmospheric helium return pressure shall be 30 mbar. |
| P-ESR-RF-ACAV:591S-FA.03.01 | The SRF Cryomodule cooling water subsystem shall be designed to utilize the supply characteristics as defined by the EIC Infrastructure Utility Requirements Document (Doc. No. EIC-IFD-RSI-012). |
| P-ESR-RF-ACAV:591S-FA.05.04 | The minimum cavity aperture radius shall be 30 mm. |
This function not yet implemented.