Electron Ion Collider
F-DET-INF-COOL.1
Requirement details, history, relationships and interfaces associated with requirement F-DET-INF-COOL.1
- CURRENT RECORD
- ARCHIVE RECORDS
- RELATIONSHIPS
- INTERFACES
Record Date: 10/10/2024 00:00 | |||
Identifier: | F-DET-INF-COOL.1 | WBS: | 6.10.10 |
Date Modified: | TBD: | FALSE | |
Status Date: | Status: | APPROVED | |
Description: | The WAH requires cooling capacity adequate for the heat generated by the detector, detector sub systems, detector support electronics and facility systems in the WAH. Comment: New airhandlers and cooling systems needed | ||
Comments: |
No archive versions
Parents | |
G-DET-INF.4 | Infrastructure systems for the collider hall shall include all power, water, environmental cooling, cryogenics, gas handling, clean compressed air delivery, space, fire protection, Helium Leak Detection, ODH Detection and any other Personnel Safety Systems, Cryo Protection, material handling and support systems required to operate the entire detector systems. |
Children | |
P-DET-INF-COOL.1 | The temperature in the WAH should be maintained between 20°C to 25°C |
P-DET-INF-COOL.2 | Relative Humidity under 50% to prevent condensation. |
P-DET-INF-COOL.3 | Where fan/ blower cooling is inadequate, water-cooled heat exchangers are required to maintain the ambient environment of enclosed electronic assemblies and equipment to a temperature of under 40°C. |