Requirement Details
Electron Ion Collider

F-DET-COMP-SC.3
Requirement details, history, relationships and interfaces associated with requirement F-DET-COMP-SC.3
CURRENT RECORD
ARCHIVE RECORDS
RELATIONSHIPS
INTERFACES
| Record Date: 03/02/2026 15:19 | |||
| Identifier: | F-DET-COMP-SC.3 | WBS: | 6.03.01.08 |
| Date Modified: | TBD: | FALSE | |
| Status Date: | Status: | Approved | |
| Description: | Slow Controls will monitor and modify operational parameters of DET subsystems. | ||
| Comments: | |||
| Record Date: 05/16/2025 17:04 | |||
| Identifier: | F-DET-COMP-SC.3 | WBS: | 6.10.09 |
| Date Modified: | TBD: | FALSE | |
| Status Date: | Status: | Approved | |
| Description: | Slow Controls will monitor and modify operational parameters of DET subsystems. | ||
| Comments: | |||
| Record Date: 05/15/2025 20:34 | |||
| Identifier: | F-DET-COMP-SC.3 | WBS: | |
| Date Modified: | TBD: | FALSE | |
| Status Date: | Status: | ||
| Description: | Slow Controls will monitor and modify operational parameters of DET subsystems. | ||
| Comments: | |||
| Record Date: 01/27/2025 16:43 | |||
| Identifier: | F-DET-COMP-SC.3 | WBS: | 6.10.09 |
| Date Modified: | TBD: | FALSE | |
| Status Date: | Status: | Approved | |
| Description: | Slow Controls will monitor and modify operational parameters of DET subsystems. | ||
| Comments: | |||
| Parents | |
| G-DET-COMP-SC.1 | The DET that will require a slow control system that provides system interlocks, interfaces, monitoring, and control. |
| Children | |
| P-DET-COMP-SC.3 | All temperatures recorded by Slow Controls shall be measured with a minimum precision of 0.1°C. |
| P-DET-COMP-SC.4 | All voltages recorded by Slow Controls shall be measured with a minimum precision of 10mV. |
| P-DET-COMP-SC.5 | All currents recorded by Slow Controls shall be measured with a minimum precision of 1mA. |
| P-DET-COMP-SC.7 | All pressures recorded by Slow Controls shall be measured with a minimum precision of 1 mbar. |
| P-DET-COMP-SC.6 | The flow of all fluids recorded by Slow Controls shall be measured with a minimum precision of 1 lpm. |
| P-DET-COMP-SC.8 | The concentration of gases in mixtures shall be recorded by Slow Controls with a minimum precision of 1%. |