| Record Date: 10/12/2026 19:31 | |||
| Identifier: | P-CTS-PSS-RAD.15 | WBS: | 6.02.04.08.01 |
| Date Modified: | TBD: | FALSE | |
| Status Date: | Status: | Approved | |
| Description: | On change from No-Access to Access mode, PSS_RAD shall verify device OFF readback within 2 s (5 s for machine-protection devices); if readback is not received, the system shall disable the upstream reach-back device and escalate with audible / visual warnings if needed. | ||
| Comments: | |||
No archive versions
| Parents | |
| No parents. | |
| Children | |
| No children. |